Service Demand Calculation for a 3-Phase 20 HP 230V HVAC Motor Unit
Calculate conductor ampacity and full-load current (FLC) for a 20 HP, 230V, 3-phase motor using NEC Table 430.250 and NEC 430.22.
Calculated strictly in accordance with NEC Table 430.250 & NEC 430.22.
On This Page
Need custom loads or multi-circuit runs?
Use the full Electrical Wire Size & Voltage Drop Calculator for deratings and printable worksheets.
Launch Full InstrumentGiven Scenario Parameters
Interactive Calculator (Pre-filled)
Adjust inputs to evaluate variations of this NEC code scenario.
Interactive Motor Demand & Conductor Sizer
Pre-loaded with NEC Table 430.250 & NEC 430.22 values
Standard NEMA motor rating
Motor operating voltage
Single or three-phase
NEC 430.6(A)(1) mandates that conductor ampacity and breaker sizing MUST be based on the NEC table values (Table 430.250), not the motor nameplate current.
Step-by-Step Solution
Formal engineering derivation citing applicable National Electrical Code articles.
Obtain Full-Load Current (FLC) from NEC Table 430.250 for 20 HP at 230V, 3-Phase: 54 Amperes.
Multiply by 125% for branch circuit conductor sizing per NEC 430.22: 54 A * 1.25 = 67.5 Amperes.
Select minimum conductor gauge: 4 AWG copper wire rated at 75°C.