Voltage Drop Calculation for 100ft 12 AWG at 20A 120V
Calculate single-phase voltage drop and percentage loss over 100 feet using 12 AWG copper under NEC recommended 3% limits.
Calculated strictly in accordance with NEC Article 210.19(A) Informational Note 4.
On This Page
Need custom loads or multi-circuit runs?
Use the full Electrical Wire Size & Voltage Drop Calculator for deratings and printable worksheets.
Launch Full InstrumentGiven Scenario Parameters
Interactive Calculator (Pre-filled)
Adjust inputs to evaluate variations of this NEC code scenario.
Electrical & Conduit Takeoff Worksheet
Date: October 7, 2026
Source: ProTrade Calculators
Circuit Parameters & Electrical Load
Calculate wire gauge, voltage drop, and NEC 310.16 ampacity for single-phase, 3-phase, and DC circuits.
Recommended Conductor & Voltage Drop Sizing
Delivers 116.87V at load terminal with 2.61% voltage drop (-3.13V drop).
Circuit Voltage Drop & Conductor Schematic
Conductor Candidate Sizing & Voltage Drop Comparison Table
COPPER Conductors| Conductor Size | Circular Mils | Base / Derated Ampacity | Voltage Drop | Voltage at Load | Max 3% Distance | Status |
|---|---|---|---|---|---|---|
| 14 AWG | 4,110 CM | 20A / 20A | 12.55V (10.46%) | 107.45V | 28.7 ft | FAIL |
| 12 AWG | 6,530 CM | 25A / 25A | 7.9V (6.58%) | 112.1V | 45.6 ft | FAIL |
| 10 AWG | 10,380 CM | 35A / 35A | 4.97V (4.14%) | 115.03V | 72.4 ft | WARNING |
| 8 AWGRecommended | 16,510 CM | 50A / 50A | 3.13V (2.61%) | 116.87V | 115.2 ft | RECOMMENDED |
| 6 AWG | 26,240 CM | 65A / 65A | 1.97V (1.64%) | 118.03V | 183.1 ft | PASS |
| 4 AWG | 41,740 CM | 85A / 85A | 1.24V (1.03%) | 118.76V | 291.2 ft | PASS |
| 3 AWG | 52,620 CM | 100A / 100A | 0.98V (0.82%) | 119.02V | 367.1 ft | PASS |
| 2 AWG | 66,360 CM | 115A / 115A | 0.78V (0.65%) | 119.22V | 463 ft | PASS |
| 1 AWG | 83,690 CM | 130A / 130A | 0.62V (0.52%) | 119.38V | 583.9 ft | PASS |
| 1/0 AWG | 105,600 CM | 150A / 150A | 0.49V (0.41%) | 119.51V | 736.7 ft | PASS |
| 2/0 AWG | 133,100 CM | 175A / 175A | 0.39V (0.33%) | 119.61V | 928.6 ft | PASS |
| 3/0 AWG | 167,800 CM | 200A / 200A | 0.31V (0.26%) | 119.69V | 1170.7 ft | PASS |
| 4/0 AWG | 211,600 CM | 230A / 230A | 0.24V (0.2%) | 119.76V | 1476.3 ft | PASS |
| 250 kcmil | 250,000 CM | 255A / 255A | 0.21V (0.18%) | 119.79V | 1744.2 ft | PASS |
| 300 kcmil | 300,000 CM | 285A / 285A | 0.17V (0.14%) | 119.83V | 2093 ft | PASS |
| 350 kcmil | 350,000 CM | 310A / 310A | 0.15V (0.13%) | 119.85V | 2441.9 ft | PASS |
| 400 kcmil | 400,000 CM | 335A / 335A | 0.13V (0.11%) | 119.87V | 2790.7 ft | PASS |
| 500 kcmil | 500,000 CM | 380A / 380A | 0.1V (0.08%) | 119.9V | 3488.4 ft | PASS |
| 600 kcmil | 600,000 CM | 420A / 420A | 0.09V (0.08%) | 119.91V | 4186 ft | PASS |
| 750 kcmil | 750,000 CM | 475A / 475A | 0.07V (0.06%) | 119.93V | 5232.6 ft | PASS |
| 1000 kcmil | 1,000,000 CM | 545A / 545A | 0.05V (0.04%) | 119.95V | 6976.7 ft | PASS |
Calculation Methodology & Mathematical Steps
Step-by-Step Solution
Formal engineering derivation citing applicable National Electrical Code articles.
Identify circular mil area for 12 AWG copper (CM = 6,530) and resistivity constant (K = 12.9 ohms-cmil/ft).
Compute voltage drop: (2 * 12.9 * 100 * 20) / 6,530 = 7.90 Volts.
Determine percentage drop: (7.90 / 120) * 100 = 6.58% (Exceeds the 3% NEC branch circuit recommendation).
Compare with NEC recommendation: 6.58% exceeds the 3% limit. Upsize conductor to 10 AWG to maintain voltage stability.