NEC Electrical Engineering & Wire Sizing Utility
NEC 3% Branch Limit • 5% Feeder System • Single & 3-Phase AC / DC • Copper vs Aluminum

Electrical Wire Size & Voltage Drop Calculator

Calculate single-phase, 3-phase, and DC voltage drop, recommended AWG/kcmil wire gauge, copper vs aluminum comparisons, and NEC Table 310.16 ampacity derating.

Circuit Parameters & Electrical Load

Calculate wire gauge, voltage drop, and NEC 310.16 ampacity for single-phase, 3-phase, and DC circuits.

Circuit System:
AC Presets:
Standard Breaker Sizes:

Recommended Conductor & Voltage Drop Sizing

240V • 50A Load • 100 ft run
Recommended Minimum Conductor Size (COPPER):
6 AWGCOPPER (26,240 CM)

Delivers 235.08V at load terminal with 2.05% voltage drop (-4.92V drop).

Actual Voltage Drop4.92V (2.05%)
Voltage at Load235.08V delivered
NEC Base Ampacity65A (65A derated)
Max 3% Distance146.5 ft limit
Copper vs. Aluminum Conductor ComparisonAt 100 ft run
Copper (Cu) Recommendation6 AWG
2.05% DropHigher conductivity
Aluminum (Al) Recommendation4 AWG
2.12% DropLower material weight/cost
Educational and reference calculator only. Conductor sizing must comply with the National Electrical Code (NEC Table 310.16), local AHJ amendments, equipment terminal temperature ratings (60°C/75°C), and short-circuit withstand ratings. Always consult a licensed electrical contractor.
Target ≤ 3% • K = 12.9 Ω·cmil/ft

Circuit Voltage Drop & Conductor Schematic

PASS (< 3%)Single-Phase AC
SOURCE240VMain Panel50ALOAD235.08VEquipment / SubDelivered100 ft One-Way Run (200 ft Loop)6 AWG COPPERΔV = -4.92V (2.05% drop)
Conductor Size6 AWG (copper)
Voltage at Load235.08 Volts (-4.92V)
Voltage Drop %2.05% (Target ≤ 3%)
Max Distance (3%)146.5 ft limit

Conductor Candidate Sizing & Voltage Drop Comparison Table

COPPER Conductors
Conductor SizeCircular MilsBase / Derated AmpacityVoltage DropVoltage at LoadMax 3% DistanceStatus
14 AWG4,110 CM20A / 20A31.39V (13.08%)208.61V22.9 ftFAIL
12 AWG6,530 CM25A / 25A19.75V (8.23%)220.25V36.4 ftFAIL
10 AWG10,380 CM35A / 35A12.43V (5.18%)227.57V57.9 ftFAIL
8 AWG16,510 CM50A / 50A7.81V (3.25%)232.19V92.1 ftWARNING
6 AWGRecommended26,240 CM65A / 65A4.92V (2.05%)235.08V146.5 ftRECOMMENDED
4 AWG41,740 CM85A / 85A3.09V (1.29%)236.91V233 ftPASS
3 AWG52,620 CM100A / 100A2.45V (1.02%)237.55V293.7 ftPASS
2 AWG66,360 CM115A / 115A1.94V (0.81%)238.06V370.4 ftPASS
1 AWG83,690 CM130A / 130A1.54V (0.64%)238.46V467.1 ftPASS
1/0 AWG105,600 CM150A / 150A1.22V (0.51%)238.78V589.4 ftPASS
2/0 AWG133,100 CM175A / 175A0.97V (0.4%)239.03V742.9 ftPASS
3/0 AWG167,800 CM200A / 200A0.77V (0.32%)239.23V936.6 ftPASS
4/0 AWG211,600 CM230A / 230A0.61V (0.25%)239.39V1181 ftPASS
250 kcmil250,000 CM255A / 255A0.52V (0.22%)239.48V1395.3 ftPASS
300 kcmil300,000 CM285A / 285A0.43V (0.18%)239.57V1674.4 ftPASS
350 kcmil350,000 CM310A / 310A0.37V (0.15%)239.63V1953.5 ftPASS
400 kcmil400,000 CM335A / 335A0.32V (0.13%)239.68V2232.6 ftPASS
500 kcmil500,000 CM380A / 380A0.26V (0.11%)239.74V2790.7 ftPASS
600 kcmil600,000 CM420A / 420A0.22V (0.09%)239.78V3348.8 ftPASS
750 kcmil750,000 CM475A / 475A0.17V (0.07%)239.83V4186 ftPASS
1000 kcmil1,000,000 CM545A / 545A0.13V (0.05%)239.87V5581.4 ftPASS
NEC Electrical Code & Safety Disclaimer: This calculation is for design and reference estimation only. Final conductor sizing must comply with the National Electrical Code (NEC Article 310, Table 310.16), local electrical amendments, terminal temperature ratings (typically 75°C), and equipment manufacturer specifications. High-voltage and feeder installations should be verified by a licensed electrical contractor.

Calculation Methodology & Mathematical Steps

1.Calculate Voltage Drop for Recommended 6 AWG (COPPER): (2.0 × 12.9 × 50A × 100 ft) ÷ 26240 CM
= 4.92V (2.05% drop, 235.08V at load)
2.Determine Maximum Distance for 3% Voltage Drop: (0.03 × 240V × 26240) ÷ (2.0 × 12.9 × 50A)
= 146.5 ft maximum one-way length

1. How Voltage Drop is Calculated (Engineering Formulas)

Voltage drop occurs when electrical current passes through the inherent resistance of a conductor over distance. The standard IEEE and National Electrical Code formulas calculate voltage drop based on conductor resistivity (K), load current (I), one-way distance (D), and conductor cross-sectional area in circular mils (CM):

Single-Phase AC & DC Circuits:

Vdrop = (2 × K × I × D) ÷ CM

Three-Phase AC Circuits:

Vdrop = (√3 × K × I × D) ÷ CM

Where K represents conductor resistivity at 75°C (12.9 Ω·cmil/ft for Copper and 21.2 Ω·cmil/ft for Aluminum), I is load current in amperes, D is one-way distance in feet, and CM is circular mils.

2. Copper vs. Aluminum Conductors: Performance & Sizing

Copper is a superior conductor with 64% lower electrical resistance than aluminum, but modern 8000-series aluminum alloy provides substantial cost and weight savings for heavy feeders:

Conductor MaterialResistivity (K @ 75°C)Standard Sizing AdvantageTypical Application
Copper (Cu)12.9 Ω·cmil/ftSmaller conduit fill, higher ampacity per gaugeBranch circuits (15A–50A), EV chargers, tight conduits
Aluminum (Al)21.2 Ω·cmil/ftLower material cost, lighter cable pulling weightMain electrical services, 100A/200A subpanels, long exterior feeders
Electrician Feeder Quick Reference

100A & 200A Subpanel Feeder Wire Sizing & Voltage Drop Table

Pre-calculated wire gauge selections, voltage drops, and percentage losses for standard 240V residential subpanels and outbuilding feeders (50 to 300 feet) under the NEC 3% recommendation:

Feeder Rating & VoltageOne-Way RunCopper Wire Gauge (75°C)Copper Drop & LossAluminum Wire Gauge (75°C)Aluminum Drop & LossNEC 3% Feeder Status
100A Subpanel (240V)50 ft#4 AWG Cu1.29V (0.54%)#2 AWG Al1.33V (0.55%)Compliant (< 3%)
100A Subpanel (240V)100 ft#3 AWG Cu2.46V (1.03%)#1 AWG Al2.53V (1.05%)Compliant (< 3%)
100A Subpanel (240V)150 ft#2 AWG Cu3.69V (1.54%)1/0 AWG Al3.78V (1.58%)Compliant (< 3%)
100A Subpanel (240V)200 ft#1 AWG Cu4.93V (2.05%)2/0 AWG Al4.99V (2.08%)Compliant (< 3%)
100A Subpanel (240V)250 ft1/0 AWG Cu6.16V (2.57%)3/0 AWG Al6.28V (2.62%)Compliant (< 3%)
100A Subpanel (240V)300 ft3/0 AWG Cu5.82V (2.43%)250 kcmil Al5.98V (2.49%)Upsized for < 3%
200A Service (240V)50 ft2/0 AWG Cu1.23V (0.51%)4/0 AWG Al1.24V (0.52%)Compliant (< 3%)
200A Service (240V)100 ft3/0 AWG Cu2.46V (1.03%)250 kcmil Al2.53V (1.05%)Compliant (< 3%)
200A Service (240V)150 ft4/0 AWG Cu3.69V (1.54%)350 kcmil Al3.72V (1.55%)Compliant (< 3%)
200A Service (240V)200 ft250 kcmil Cu4.92V (2.05%)500 kcmil Al4.96V (2.07%)Compliant (< 3%)

3. 120V vs. 240V Circuits: Why 120V Drops Twice as Fast

Because voltage drop percentage is relative to system voltage (Drop % = Vdrop ÷ Vsystem), a 120V circuit suffers twice the percentage drop of a 240V circuit carrying the exact same current over the same distance:

120V Circuit (15A @ 100 ft, 14 AWG)

Voltage drop is 9.42V, which equals a severe 7.85% drop (delivers only 110.58V). Requires upsizing to 10 AWG or 8 AWG to maintain 3% or lower drop.

240V Circuit (15A @ 100 ft, 14 AWG)

Voltage drop is still 9.42V, but represents only a 3.92% drop (delivers 230.58V).

4. NEC Voltage Drop Recommendations (3% Branch / 5% Total)

While the National Electrical Code does not mandate voltage drop limits as a hard violation in all residential installations, it specifies critical engineering recommendations:

  • NEC 210.19(A) Informational Note 4: Branch circuits should be sized for a maximum voltage drop of 3% at the furthest outlet.
  • NEC 215.2(A)(1) Informational Note 2: Feeder conductors should not exceed 3% drop, and total drop across both feeder and branch conductors should not exceed 5%.
  • Equipment Protection: Motors subjected to low voltage draw excessive current and overheat; sensitive electronics and LED drivers flicker or shut down when voltage drops below 95% of nominal.

5. Level 2 EV Charger Wire Sizing & Continuous Loads

Electric vehicle charging stations are classified as continuous loads under NEC Article 625, requiring circuit conductors and overcurrent devices to be sized at 125% of the charger's rated amperage:

EV Charger Continuous Load125% Design CurrentBreaker SizeMin Copper Wire (Up to 75 ft)Long Run Copper (100–150 ft)
32A Charger40A40A Breaker8 AWG Copper6 AWG Copper
40A Charger50A50A Breaker6 AWG Copper4 AWG Copper
48A Charger (Hardwired)60A60A Breaker6 AWG (90°C) or 4 AWG4 AWG or 2 AWG Copper

6. 12V & 24V DC Wire Gauge Distance Chart (Marine, Solar & RV)

In low-voltage DC systems, voltage drop occurs much faster than in 120V/240V AC systems because system voltage is low. Per ABYC E-11 standards and NEC 690 (Solar PV), critical electronics and battery charging circuits must maintain ≤ 3% drop (0.36V on 12V), while general lighting and bilge circuits permit ≤ 10% drop (1.20V on 12V).

Copper Wire GaugeCircular Mils10A Load (3% Drop)10A Load (10% Drop)20A Load (3% Drop)20A Load (10% Drop)
14 AWG4,110 CM5.7 ft19.1 ft2.9 ft9.6 ft
12 AWG6,530 CM9.1 ft30.4 ft4.6 ft15.2 ft
10 AWG10,380 CM14.5 ft48.3 ft7.2 ft24.1 ft
8 AWG16,510 CM23.0 ft76.8 ft11.5 ft38.4 ft
6 AWG26,240 CM36.6 ft122.0 ft18.3 ft61.0 ft
4 AWG41,740 CM58.2 ft194.1 ft29.1 ft97.1 ft
2 AWG66,360 CM92.6 ft308.7 ft46.3 ft154.3 ft

* Distances represent one-way cable run length in feet. For 24V DC systems, double the maximum allowed run distance.

7. Sizing 100A & 200A Subpanel Feeders for Workshops & Garages

When running electrical subpanels to detached garages, workshops, or outbuildings over distances of 100 to 300 feet, voltage drop almost always dictates conductor sizing before thermal ampacity:

  • 100A Subpanel (50 ft run): 4 AWG Copper or 2 AWG Aluminum (0.8% drop).
  • 100A Subpanel (150 ft run): 1 AWG Copper or 2/0 Aluminum (2.3% drop).
  • 100A Subpanel (300 ft run): 3/0 Copper or 250 kcmil Aluminum (2.8% drop).
  • 200A Service (200 ft run): 4/0 Copper or 350 kcmil Aluminum (2.4% drop).

8. Common Electrical Wire Sizing Mistakes to Avoid

Critical Safety & Code Traps

  • Ignoring Terminal Temperature Ratings: Breakers and lugs rated for 75°C must use the 75°C column of NEC Table 310.16, even if using 90°C THHN wire.
  • Forgetting Rooftop Solar Conduit Derating: Exterior conduits on hot rooftops can reach 140°F+, requiring up to 50% ampacity derating.
  • Using Small Aluminum Conductors: Aluminum smaller than 8 AWG is restricted in residential branch wiring due to oxidation and thermal expansion hazards.
Technical Master Reference

The Electrician's Guide to Voltage Drop: Formulas & Code Limits

In-depth reference covering single-phase and 3-phase voltage drop equations, NEC 210.19/215.2 recommendations (3% branch, 5% feeder), and circular mil resistance constants.

Read Master Guide

10. Real-World NEC Calculation Scenarios

Step-by-step mathematical solutions and code citations for wire sizing and voltage drop problems:

9. Frequently Asked Questions

What is the maximum acceptable voltage drop according to the National Electrical Code (NEC)?

The NEC recommends a maximum voltage drop of 3% on branch circuits (NEC 210.19(A) Informational Note 4) and a maximum total voltage drop of 5% across both the feeder and branch circuit combined (NEC 215.2(A)(1) Informational Note 2) to ensure reasonable efficiency of operation.

What is the difference between single-phase and 3-phase voltage drop formulas?

Single-phase circuits require current to travel out along the hot conductor and return via the neutral (a 2-wire round trip), using the multiplier 2.0: Vdrop = (2 × K × I × D) / CM. Three-phase circuits share return currents among phases 120° apart, reducing effective resistance by using the multiplier √3 (~1.732): Vdrop = (√3 × K × I × D) / CM.

When should I use aluminum wire instead of copper?

Aluminum (typically 8000-series alloy such as XHHW-2 or USE-2) is commonly used for heavy feeder circuits (100A, 150A, 200A subpanels and main services) because it is significantly lighter and less expensive than copper. However, because aluminum has higher resistivity (K = 21.2 vs 12.9 for copper), it requires upsizing by approximately one to two AWG gauge sizes.

Why does voltage drop matter for EV chargers and subpanels?

Level 2 EV chargers draw heavy continuous loads (e.g. 48A on a 60A circuit) for 4 to 10 hours continuously. Excessive voltage drop results in power wasted as heat in walls or conduit, slower vehicle charging rates, and potential thermal tripping of breakers.

How does ambient temperature affect conductor ampacity?

Conductor insulation ratings (60°C, 75°C, 90°C) are calibrated for a 30°C (86°F) ambient baseline. When cables run through hot attics, commercial roofs, or exterior conduit in direct sunlight (temperatures of 104°F to 140°F), NEC Table 310.15(B)(1) requires derating conductor ampacity by 10% to 50% to prevent insulation degradation.

What is circular mils (CM) and why is it used to size wire?

Circular mils (CM) is a standard unit of cross-sectional area for electrical conductors. One circular mil equals the area of a circle with a diameter of 1 mil (0.001 inch). Larger conductors have higher CM values, which reduces electrical resistance and lowers voltage drop.