Branch Circuit Conductor & Breaker Sizing for 15 HP 460V 3-Phase Motor
Calculate minimum conductor ampacity and inverse time breaker sizing for a 15 HP 460V 3-phase motor under NEC 430.22 and 430.52.
Calculated strictly in accordance with NEC Table 430.250, NEC 430.22, & Table 430.52.
On This Page
Need custom loads or multi-circuit runs?
Use the full Electrical Wire Size & Voltage Drop Calculator for deratings and printable worksheets.
Launch Full InstrumentGiven Scenario Parameters
Interactive Calculator (Pre-filled)
Adjust inputs to evaluate variations of this NEC code scenario.
Interactive Motor Demand & Conductor Sizer
Pre-loaded with NEC Table 430.250 & NEC 430.22 values
Standard NEMA motor rating
Motor operating voltage
Single or three-phase
NEC 430.6(A)(1) mandates that conductor ampacity and breaker sizing MUST be based on the NEC table values (Table 430.250), not the motor nameplate current.
Step-by-Step Solution
Formal engineering derivation citing applicable National Electrical Code articles.
Locate Full-Load Current (FLC) from NEC Table 430.250: 21 Amperes.
Conductor Ampacity: 21 A * 1.25 = 26.25 Amperes (Select minimum 10 AWG copper rated at 75°C).
Short-Circuit Protection (Inverse Time Breaker per Table 430.52 at 250%): 21 A * 2.50 = 52.5 Amperes.
Select standard breaker size per NEC 240.6(A): Next standard size up is a 60 Ampere circuit breaker.