45 kVA 3-Phase Transformer Primary and Secondary Full-Load Amps
Calculate primary (480V) and secondary (208V) full-load current (FLC) and minimum overcurrent protection for a 45 kVA 3-phase dry-type transformer under NEC 450.3.
Calculated strictly in accordance with NEC Article 450.3(B) & Table 450.3(B).
On This Page
Need custom loads or multi-circuit runs?
Use the full Residential Electrical Service Load Calculator for deratings and printable worksheets.
Launch Full InstrumentGiven Scenario Parameters
Interactive Calculator (Pre-filled)
Adjust inputs to evaluate variations of this NEC code scenario.
Interactive Electric Load Calculator
Pre-loaded with NEC 220.51 & 424.3(B) parameters
Nameplate wattage of the heating unit or load
Line-to-line or line-to-neutral
NEC 424.3(B) mandates that fixed electric space heating equipment branch circuits must be sized at 125% of the total load current.
Step-by-Step Solution
Formal engineering derivation citing applicable National Electrical Code articles.
Calculate 480V Primary FLC: 45,000 / (480 * 1.732) = 54.13 Amperes.
Calculate 208V Secondary FLC: 45,000 / (208 * 1.732) = 124.91 Amperes.
Determine primary overcurrent protection per Table 450.3(B) at 125%: 54.13 A * 1.25 = 67.66 A (Next standard size up: 70A breaker).