Three-Phase 480V Feeder Voltage Drop: 500ft 100A
Calculate 3-phase line-to-line voltage drop and percentage loss over 500 feet for a 100A 480V industrial feeder under NEC recommendations.
Calculated strictly in accordance with NEC Article 215.2(A)(1) Informational Note 2.
On This Page
Need custom loads or multi-circuit runs?
Use the full Electrical Wire Size & Voltage Drop Calculator for deratings and printable worksheets.
Launch Full InstrumentGiven Scenario Parameters
Interactive Calculator (Pre-filled)
Adjust inputs to evaluate variations of this NEC code scenario.
Electrical & Conduit Takeoff Worksheet
Date: October 7, 2026
Source: ProTrade Calculators
Circuit Parameters & Electrical Load
Calculate wire gauge, voltage drop, and NEC 310.16 ampacity for single-phase, 3-phase, and DC circuits.
Recommended Conductor & Voltage Drop Sizing
Delivers 466.65V at load terminal with 2.78% voltage drop (-13.35V drop).
Circuit Voltage Drop & Conductor Schematic
Conductor Candidate Sizing & Voltage Drop Comparison Table
COPPER Conductors| Conductor Size | Circular Mils | Base / Derated Ampacity | Voltage Drop | Voltage at Load | Max 3% Distance | Status |
|---|---|---|---|---|---|---|
| 14 AWG | 4,110 CM | 20A / 20A | 271.82V (56.63%) | 208.18V | 26.5 ft | FAIL |
| 12 AWG | 6,530 CM | 25A / 25A | 171.08V (35.64%) | 308.92V | 42.1 ft | FAIL |
| 10 AWG | 10,380 CM | 35A / 35A | 107.63V (22.42%) | 372.37V | 66.9 ft | FAIL |
| 8 AWG | 16,510 CM | 50A / 50A | 67.67V (14.1%) | 412.33V | 106.4 ft | FAIL |
| 6 AWG | 26,240 CM | 65A / 65A | 42.58V (8.87%) | 437.42V | 169.1 ft | FAIL |
| 4 AWG | 41,740 CM | 85A / 85A | 26.77V (5.58%) | 453.23V | 269 ft | FAIL |
| 3 AWG | 52,620 CM | 100A / 100A | 21.23V (4.42%) | 458.77V | 339.1 ft | WARNING |
| 2 AWG | 66,360 CM | 115A / 115A | 16.84V (3.51%) | 463.16V | 427.7 ft | WARNING |
| 1 AWGRecommended | 83,690 CM | 130A / 130A | 13.35V (2.78%) | 466.65V | 539.4 ft | RECOMMENDED |
| 1/0 AWG | 105,600 CM | 150A / 150A | 10.58V (2.2%) | 469.42V | 680.6 ft | PASS |
| 2/0 AWG | 133,100 CM | 175A / 175A | 8.39V (1.75%) | 471.61V | 857.8 ft | PASS |
| 3/0 AWG | 167,800 CM | 200A / 200A | 6.66V (1.39%) | 473.34V | 1081.4 ft | PASS |
| 4/0 AWG | 211,600 CM | 230A / 230A | 5.28V (1.1%) | 474.72V | 1363.7 ft | PASS |
| 250 kcmil | 250,000 CM | 255A / 255A | 4.47V (0.93%) | 475.53V | 1611.2 ft | PASS |
| 300 kcmil | 300,000 CM | 285A / 285A | 3.72V (0.78%) | 476.28V | 1933.5 ft | PASS |
| 350 kcmil | 350,000 CM | 310A / 310A | 3.19V (0.66%) | 476.81V | 2255.7 ft | PASS |
| 400 kcmil | 400,000 CM | 335A / 335A | 2.79V (0.58%) | 477.21V | 2577.9 ft | PASS |
| 500 kcmil | 500,000 CM | 380A / 380A | 2.23V (0.46%) | 477.77V | 3222.4 ft | PASS |
| 600 kcmil | 600,000 CM | 420A / 420A | 1.86V (0.39%) | 478.14V | 3866.9 ft | PASS |
| 750 kcmil | 750,000 CM | 475A / 475A | 1.49V (0.31%) | 478.51V | 4833.6 ft | PASS |
| 1000 kcmil | 1,000,000 CM | 545A / 545A | 1.12V (0.23%) | 478.88V | 6444.8 ft | PASS |
Calculation Methodology & Mathematical Steps
Step-by-Step Solution
Formal engineering derivation citing applicable National Electrical Code articles.
Select 1 AWG copper conductor (CM = 83,690) with copper constant K = 12.9.
Apply 3-phase formula: (1.732 * 12.9 * 500 * 100) / 83,690 = 13.34 Volts drop.
Calculate percentage drop: (13.34 / 480) * 100 = 2.78%.
Compare against code limits: 2.78% is within the NEC recommended 3% feeder limit.