NEC Article 215.2(A)(1) Informational Note 2Worked ExampleElectrical

Three-Phase 480V Feeder Voltage Drop: 500ft 100A

Calculate 3-phase line-to-line voltage drop and percentage loss over 500 feet for a 100A 480V industrial feeder under NEC recommendations.

Direct Answer
13.34 V Drop (2.78% Loss - Compliant with NEC 3% Feeder Recommendation)

Calculated strictly in accordance with NEC Article 215.2(A)(1) Informational Note 2.

Open Calculator

Given Scenario Parameters

distance500
wire Gauge1 AWG
current100
voltage480
phase3

Interactive Calculator (Pre-filled)

Adjust inputs to evaluate variations of this NEC code scenario.

Circuit Parameters & Electrical Load

Calculate wire gauge, voltage drop, and NEC 310.16 ampacity for single-phase, 3-phase, and DC circuits.

Circuit System:
AC Presets:
Standard Breaker Sizes:
Verified NEC Code Proof Available (NEC 215.2(A)(1) & Chapter 9 Table 9)Configuration matches: 500ft 480V 3-Phase 100A Commercial Feeder Proof
Inspect Code Proof

Recommended Conductor & Voltage Drop Sizing

480V • 100A Load • 500 ft run
Recommended Minimum Conductor Size (COPPER):
1 AWGCOPPER (83,690 CM)

Delivers 466.65V at load terminal with 2.78% voltage drop (-13.35V drop).

Actual Voltage Drop13.35V (2.78%)
Voltage at Load466.65V delivered
NEC Base Ampacity130A (130A derated)
Max 3% Distance539.4 ft limit
Copper vs. Aluminum Conductor ComparisonAt 500 ft run
Copper (Cu) Recommendation1 AWG
2.78% DropHigher conductivity
Aluminum (Al) Recommendation2/0 AWG
2.87% DropLower material weight/cost
Educational and reference calculator only. Conductor sizing must comply with the National Electrical Code (NEC Table 310.16), local AHJ amendments, equipment terminal temperature ratings (60°C/75°C), and short-circuit withstand ratings. Always consult a licensed electrical contractor.
Target ≤ 3% • K = 12.9 Ω·cmil/ft

Circuit Voltage Drop & Conductor Schematic

PASS (< 3%)3-Phase AC
SOURCE480VMain Panel100ALOAD466.65VEquipment / SubDelivered500 ft One-Way Run (1000 ft Loop)1 AWG COPPERΔV = -13.35V (2.78% drop)
Conductor Size1 AWG (copper)
Voltage at Load466.65 Volts (-13.35V)
Voltage Drop %2.78% (Target ≤ 3%)
Max Distance (3%)539.4 ft limit

Conductor Candidate Sizing & Voltage Drop Comparison Table

COPPER Conductors
Conductor SizeCircular MilsBase / Derated AmpacityVoltage DropVoltage at LoadMax 3% DistanceStatus
14 AWG4,110 CM20A / 20A271.82V (56.63%)208.18V26.5 ftFAIL
12 AWG6,530 CM25A / 25A171.08V (35.64%)308.92V42.1 ftFAIL
10 AWG10,380 CM35A / 35A107.63V (22.42%)372.37V66.9 ftFAIL
8 AWG16,510 CM50A / 50A67.67V (14.1%)412.33V106.4 ftFAIL
6 AWG26,240 CM65A / 65A42.58V (8.87%)437.42V169.1 ftFAIL
4 AWG41,740 CM85A / 85A26.77V (5.58%)453.23V269 ftFAIL
3 AWG52,620 CM100A / 100A21.23V (4.42%)458.77V339.1 ftWARNING
2 AWG66,360 CM115A / 115A16.84V (3.51%)463.16V427.7 ftWARNING
1 AWGRecommended83,690 CM130A / 130A13.35V (2.78%)466.65V539.4 ftRECOMMENDED
1/0 AWG105,600 CM150A / 150A10.58V (2.2%)469.42V680.6 ftPASS
2/0 AWG133,100 CM175A / 175A8.39V (1.75%)471.61V857.8 ftPASS
3/0 AWG167,800 CM200A / 200A6.66V (1.39%)473.34V1081.4 ftPASS
4/0 AWG211,600 CM230A / 230A5.28V (1.1%)474.72V1363.7 ftPASS
250 kcmil250,000 CM255A / 255A4.47V (0.93%)475.53V1611.2 ftPASS
300 kcmil300,000 CM285A / 285A3.72V (0.78%)476.28V1933.5 ftPASS
350 kcmil350,000 CM310A / 310A3.19V (0.66%)476.81V2255.7 ftPASS
400 kcmil400,000 CM335A / 335A2.79V (0.58%)477.21V2577.9 ftPASS
500 kcmil500,000 CM380A / 380A2.23V (0.46%)477.77V3222.4 ftPASS
600 kcmil600,000 CM420A / 420A1.86V (0.39%)478.14V3866.9 ftPASS
750 kcmil750,000 CM475A / 475A1.49V (0.31%)478.51V4833.6 ftPASS
1000 kcmil1,000,000 CM545A / 545A1.12V (0.23%)478.88V6444.8 ftPASS
NEC Electrical Code & Safety Disclaimer: This calculation is for design and reference estimation only. Final conductor sizing must comply with the National Electrical Code (NEC Article 310, Table 310.16), local electrical amendments, terminal temperature ratings (typically 75°C), and equipment manufacturer specifications. High-voltage and feeder installations should be verified by a licensed electrical contractor.

Calculation Methodology & Mathematical Steps

1.Calculate Voltage Drop for Recommended 1 AWG (COPPER): (√3 (1.732) × 12.9 × 100A × 500 ft) ÷ 83690 CM
= 13.35V (2.78% drop, 466.65V at load)
2.Determine Maximum Distance for 3% Voltage Drop: (0.03 × 480V × 83690) ÷ (√3 (1.732) × 12.9 × 100A)
= 539.4 ft maximum one-way length

Step-by-Step Solution

Formal engineering derivation citing applicable National Electrical Code articles.

Governing Code Equation
VD = (1.732 * K * L * I) / CM
Citing NEC Article 215.2(A)(1) Informational Note 2
1

Select 1 AWG copper conductor (CM = 83,690) with copper constant K = 12.9.

2

Apply 3-phase formula: (1.732 * 12.9 * 500 * 100) / 83,690 = 13.34 Volts drop.

3

Calculate percentage drop: (13.34 / 480) * 100 = 2.78%.

4

Compare against code limits: 2.78% is within the NEC recommended 3% feeder limit.

Conclusion: 13.34 V Drop (2.78% Loss - Compliant with NEC 3% Feeder Recommendation)
NEC Article 215.2(A)(1) Informational Note 2