Subpanel Feeder Voltage Drop Calculation: 250ft 6 AWG at 50A 240V
Calculate feeder voltage drop over 250 feet for a 50A 240V subpanel using 6 AWG copper under NEC 215.2 recommendations.
Calculated strictly in accordance with NEC Article 215.2(A)(1) Informational Note 2.
On This Page
Need custom loads or multi-circuit runs?
Use the full Electrical Wire Size & Voltage Drop Calculator for deratings and printable worksheets.
Launch Full InstrumentGiven Scenario Parameters
Interactive Calculator (Pre-filled)
Adjust inputs to evaluate variations of this NEC code scenario.
Electrical & Conduit Takeoff Worksheet
Date: October 7, 2026
Source: ProTrade Calculators
Circuit Parameters & Electrical Load
Calculate wire gauge, voltage drop, and NEC 310.16 ampacity for single-phase, 3-phase, and DC circuits.
Recommended Conductor & Voltage Drop Sizing
Delivers 233.87V at load terminal with 2.55% voltage drop (-6.13V drop).
Circuit Voltage Drop & Conductor Schematic
Conductor Candidate Sizing & Voltage Drop Comparison Table
COPPER Conductors| Conductor Size | Circular Mils | Base / Derated Ampacity | Voltage Drop | Voltage at Load | Max 3% Distance | Status |
|---|---|---|---|---|---|---|
| 14 AWG | 4,110 CM | 20A / 20A | 78.47V (32.7%) | 161.53V | 22.9 ft | FAIL |
| 12 AWG | 6,530 CM | 25A / 25A | 49.39V (20.58%) | 190.61V | 36.4 ft | FAIL |
| 10 AWG | 10,380 CM | 35A / 35A | 31.07V (12.95%) | 208.93V | 57.9 ft | FAIL |
| 8 AWG | 16,510 CM | 50A / 50A | 19.53V (8.14%) | 220.47V | 92.1 ft | FAIL |
| 6 AWG | 26,240 CM | 65A / 65A | 12.29V (5.12%) | 227.71V | 146.5 ft | FAIL |
| 4 AWG | 41,740 CM | 85A / 85A | 7.73V (3.22%) | 232.27V | 233 ft | WARNING |
| 3 AWGRecommended | 52,620 CM | 100A / 100A | 6.13V (2.55%) | 233.87V | 293.7 ft | RECOMMENDED |
| 2 AWG | 66,360 CM | 115A / 115A | 4.86V (2.03%) | 235.14V | 370.4 ft | PASS |
| 1 AWG | 83,690 CM | 130A / 130A | 3.85V (1.6%) | 236.15V | 467.1 ft | PASS |
| 1/0 AWG | 105,600 CM | 150A / 150A | 3.05V (1.27%) | 236.95V | 589.4 ft | PASS |
| 2/0 AWG | 133,100 CM | 175A / 175A | 2.42V (1.01%) | 237.58V | 742.9 ft | PASS |
| 3/0 AWG | 167,800 CM | 200A / 200A | 1.92V (0.8%) | 238.08V | 936.6 ft | PASS |
| 4/0 AWG | 211,600 CM | 230A / 230A | 1.52V (0.63%) | 238.48V | 1181 ft | PASS |
| 250 kcmil | 250,000 CM | 255A / 255A | 1.29V (0.54%) | 238.71V | 1395.3 ft | PASS |
| 300 kcmil | 300,000 CM | 285A / 285A | 1.08V (0.45%) | 238.92V | 1674.4 ft | PASS |
| 350 kcmil | 350,000 CM | 310A / 310A | 0.92V (0.38%) | 239.08V | 1953.5 ft | PASS |
| 400 kcmil | 400,000 CM | 335A / 335A | 0.81V (0.34%) | 239.19V | 2232.6 ft | PASS |
| 500 kcmil | 500,000 CM | 380A / 380A | 0.65V (0.27%) | 239.35V | 2790.7 ft | PASS |
| 600 kcmil | 600,000 CM | 420A / 420A | 0.54V (0.23%) | 239.46V | 3348.8 ft | PASS |
| 750 kcmil | 750,000 CM | 475A / 475A | 0.43V (0.18%) | 239.57V | 4186 ft | PASS |
| 1000 kcmil | 1,000,000 CM | 545A / 545A | 0.32V (0.13%) | 239.68V | 5581.4 ft | PASS |
Calculation Methodology & Mathematical Steps
Step-by-Step Solution
Formal engineering derivation citing applicable National Electrical Code articles.
Identify circular mil area for 6 AWG copper (CM = 26,240) and resistivity constant (K = 12.9 ohms-cmil/ft).
Compute feeder voltage drop: (2 * 12.9 * 250 * 50) / 26,240 = 12.29 Volts.
Determine percentage drop: (12.29 / 240) * 100 = 5.12%.
Compare with NEC recommendation: 5.12% exceeds the recommended 3% maximum. Upsize conductor to 4 AWG copper to keep drop below 3% (7.73V / 3.22%).