NEC Table 314.16(A) & 314.16(B)Worked ExampleElectrical

4x4x2-1/8 Square Deep Metal Box Conductor & Device Capacity

Determine maximum conductor capacity and device allowance for a 4x4x2-1/8 inch deep square metal box (30.3 cu in) under NEC 314.16.

Direct Answer
30.3 cu. in. Volume: Maximum 13 isolated 12 AWG wires (or 10 wires with 1 receptacle & ground)

Calculated strictly in accordance with NEC Table 314.16(A) & 314.16(B).

Open Calculator

Given Scenario Parameters

conductors1 conductors
conduit TypeBox Fill

Interactive Calculator (Pre-filled)

Adjust inputs to evaluate variations of this NEC code scenario.

Conduit Cross-Section CAD Blueprint

Trade Size: 3/4″ EMT

SAFE CODE CAPACITY
12345678910111213Fill: 32.44% (NEC Max 40%)Wire Area: 0.1729 in² / Total Area: 0.533 in²
Conductors: 13 Total
Conduit Size3/4″ EMT
Fill Area0.1729 in²
Fill %32.44%
01

Conduit & Wire Schedule

Quick Presets:
Conductor Wire List (13 Wires)
Conduit Sizing Schedule & Trade Size
32.4% Fill (Limit 40%)
Recommended Trade Size
3/4EMT
13 Conductors • Total Wire Area: 0.1729 sq in
Raceway Fill Telemetry
Conduit Internal Area:0.5330 sq in
Max Code Fill Capacity:40%
Actual Fill Utilization:32.4%

Step-by-Step Solution

Formal engineering derivation citing applicable National Electrical Code articles.

Governing Code Equation
Max 12 AWG Conductors = Total Volume / 2.25 cu in
Citing NEC Table 314.16(A) & 314.16(B)
1

Per NEC Table 314.16(A), a 4 x 4 x 2-1/8 inch square metal box provides 30.3 cubic inches of interior volume.

2

Volume allowance per 12 AWG conductor is 2.25 cubic inches.

3

Compute maximum pure conductor capacity: 30.3 cu. in. / 2.25 cu. in. = 13 conductors (29.25 cu. in.).

4

When installing a receptacle (deduct 2 allowances = 4.5 cu in) and ground wire (deduct 1 allowance = 2.25 cu in), maximum remaining 12 AWG conductors is (30.3 - 6.75) / 2.25 = 10 conductors.

Conclusion: 30.3 cu. in. Volume: Maximum 13 isolated 12 AWG wires (or 10 wires with 1 receptacle & ground)
NEC Table 314.16(A) & 314.16(B)