Conduit Sizing for Four 500 kcmil THHN Conductors in RMC
Size Rigid Metal Conduit (RMC) for four 500 kcmil THHN copper conductors using NEC Chapter 9 Tables 1, 4, and 5.
Calculated strictly in accordance with NEC Chapter 9 Table 1 & Table 4 (RMC).
On This Page
Need custom loads or multi-circuit runs?
Use the full Electrical Conduit Fill Calculator for deratings and printable worksheets.
Launch Full InstrumentGiven Scenario Parameters
Interactive Calculator (Pre-filled)
Adjust inputs to evaluate variations of this NEC code scenario.
Electrical & Conduit Takeoff Worksheet
Date: October 7, 2026
Source: ProTrade Calculators
Conduit Cross-Section CAD Blueprint
Trade Size: 3″ RMC
Conduit & Wire Schedule
Step-by-Step Solution
Formal engineering derivation citing applicable National Electrical Code articles.
Find area of one 500 kcmil THHN conductor from NEC Table 5: 0.7073 sq. in.
Multiply by 4 conductors: 4 * 0.7073 = 2.8292 sq. in.
Consult NEC Table 4 RMC 40% fill column: 3-inch RMC allows 2.95 sq. in., satisfying the 2.8292 sq. in. requirement.