Conduit Sizing Verification: Six 10 AWG THHN Wires in 1/2-Inch EMT
Verify code compliance and percentage raceway fill for six 10 AWG THHN conductors inside 1/2-inch EMT per NEC Chapter 9.
Calculated strictly in accordance with NEC Chapter 9 Table 1, Table 4, & Table C.1.
On This Page
Need custom loads or multi-circuit runs?
Use the full Electrical Conduit Fill Calculator for deratings and printable worksheets.
Launch Full InstrumentGiven Scenario Parameters
Interactive Calculator (Pre-filled)
Adjust inputs to evaluate variations of this NEC code scenario.
Electrical & Conduit Takeoff Worksheet
Date: October 7, 2026
Source: ProTrade Calculators
Conduit Cross-Section CAD Blueprint
Trade Size: 3/4″ EMT
Conduit & Wire Schedule
Step-by-Step Solution
Formal engineering derivation citing applicable National Electrical Code articles.
Find cross-sectional area of 10 AWG THHN from Table 5: 0.0211 sq. in.
Calculate total area for 6 wires: 6 * 0.0211 = 0.1266 sq. in.
Check 1/2-inch EMT 40% fill limit from Table 4: 0.122 sq. in.
Evaluate: 0.1266 sq. in. exceeds the 0.122 sq. in. allowance (Fill is 41.5%). 1/2-inch EMT is undersized; upsizing to 3/4-inch EMT is required.