200-Ampere Single-Family Residential Service Feeder Sizing
Calculate minimum service conductor ampacity for a 200A 120/240V dwelling service using NEC Table 310.12.
Calculated strictly in accordance with NEC Article 310.12 & Table 310.12.
On This Page
Need custom loads or multi-circuit runs?
Use the full Residential Electrical Service Load Calculator for deratings and printable worksheets.
Launch Full InstrumentGiven Scenario Parameters
Interactive Calculator (Pre-filled)
Adjust inputs to evaluate variations of this NEC code scenario.
Interactive Electric Load Calculator
Pre-loaded with NEC 220.51 & 424.3(B) parameters
Nameplate wattage of the heating unit or load
Line-to-line or line-to-neutral
NEC 424.3(B) mandates that fixed electric space heating equipment branch circuits must be sized at 125% of the total load current.
Step-by-Step Solution
Formal engineering derivation citing applicable National Electrical Code articles.
Per NEC 310.12, dwelling unit service and feeder conductors are permitted to be sized at 83% of the service rating.
Calculate 83% of 200 Amperes: 200 A * 0.83 = 166 Amperes minimum ampacity.
Select conductor from NEC Table 310.12: 2/0 AWG Copper or 4/0 AWG Aluminum rated at 75°C satisfies the 200A dwelling service requirement.