Grounding Electrode Conductor (GEC) Sizing for 200A Service
Size the Grounding Electrode Conductor for a 200A residential service with 2/0 copper service conductors using NEC Table 250.66.
Calculated strictly in accordance with NEC Article 250.66 & Table 250.66.
On This Page
Need custom loads or multi-circuit runs?
Use the full Residential Electrical Service Load Calculator for deratings and printable worksheets.
Launch Full InstrumentGiven Scenario Parameters
Interactive Calculator (Pre-filled)
Adjust inputs to evaluate variations of this NEC code scenario.
Interactive Electric Load Calculator
Pre-loaded with NEC 220.51 & 424.3(B) parameters
Nameplate wattage of the heating unit or load
Line-to-line or line-to-neutral
NEC 424.3(B) mandates that fixed electric space heating equipment branch circuits must be sized at 125% of the total load current.
Step-by-Step Solution
Formal engineering derivation citing applicable National Electrical Code articles.
Identify service entrance conductor gauge: 2/0 AWG Copper.
Consult NEC Table 250.66 under '2/0 or 3/0 AWG Copper'.
Read required GEC size: 4 AWG Copper (or 2 AWG Aluminum).
Special electrode exceptions: Ground rods require maximum 6 AWG copper (NEC 250.66(A)); concrete-encased electrodes require maximum 4 AWG copper (NEC 250.66(B)).