Household Electric Range Feeder Neutral Conductor Sizing
Calculate the maximum unbalance neutral feeder load for a household electric range using the 70% demand factor under NEC 220.61(B).
Calculated strictly in accordance with NEC Article 220.61(B)(1).
On This Page
Need custom loads or multi-circuit runs?
Use the full Residential Electrical Service Load Calculator for deratings and printable worksheets.
Launch Full InstrumentGiven Scenario Parameters
Interactive Calculator (Pre-filled)
Adjust inputs to evaluate variations of this NEC code scenario.
Interactive Electric Load Calculator
Pre-loaded with NEC 220.51 & 424.3(B) parameters
Nameplate wattage of the heating unit or load
Line-to-line or line-to-neutral
NEC 424.3(B) mandates that fixed electric space heating equipment branch circuits must be sized at 125% of the total load current.
Step-by-Step Solution
Formal engineering derivation citing applicable National Electrical Code articles.
Per NEC 220.61(B)(1), the feeder neutral demand for household electric ranges is assessed at 70% of the calculated demand from Table 220.55.
Base range demand from Table 220.55 = 8,000 Watts.
Calculate neutral demand: 8,000 W * 0.70 = 5,600 Watts.
Compute neutral current: 5,600 W / 240 V = 23.33 Amperes.