Calculated Service Load for an Electric Clothes Dryer Rated 5,000W at 240V
Calculate service feeder load for an electric clothes dryer under NEC Article 220.54 minimum requirements.
Calculated strictly in accordance with NEC Article 220.54.
On This Page
Need custom loads or multi-circuit runs?
Use the full Residential Electrical Service Load Calculator for deratings and printable worksheets.
Launch Full InstrumentGiven Scenario Parameters
Interactive Calculator (Pre-filled)
Adjust inputs to evaluate variations of this NEC code scenario.
Interactive Electric Load Calculator
Pre-loaded with NEC 220.51 & 424.3(B) parameters
Nameplate wattage of the heating unit or load
Line-to-line or line-to-neutral
NEC 424.3(B) mandates that fixed electric space heating equipment branch circuits must be sized at 125% of the total load current.
Step-by-Step Solution
Formal engineering derivation citing applicable National Electrical Code articles.
Per NEC 220.54, the feeder demand for a residential electric dryer must be a minimum of 5,000 Watts or the nameplate rating, whichever is higher.
Nameplate is 5,000 W, so calculation load = 5,000 Watts.
Compute feeder ampacity: 5,000 W / 240 V = 20.83 Amperes.
Select minimum branch circuit rating per NEC 250: Minimum 30 Ampere circuit with 10 AWG copper.